This paper evaluates a state-space methodology of a multi-input multi-output (MIMO) control strategy using a 2 × 2 tightly coupled scenario applied to a physical gas turbine fuel cell hybrid power system. A centralized MIMO controller was preferred compared to a decentralized control approach because previous simulation studies showed that the coupling effect identified during the simultaneous control of the turbine speed and cathode airflow was better minimized. The MIMO controller was developed using a state-space dynamic model of the system that was derived using first-order transfer functions empirically obtained through experimental tests. The controller performance was evaluated in terms of disturbance rejection through perturbations in the gas turbine operation, and setpoint tracking maneuver through turbine speed and cathode airflow steps. The experimental results illustrate that a multicoordination control strategy was able to mitigate the coupling of each actuator to each output during the simultaneous control of the system, and improved the overall system performance during transient conditions. On the other hand, the controller showed different performance during validation in simulation environment compared to validation in the physical facility, which will require a better dynamic modeling of the system for the implementation of future multivariable control strategies.
Introduction
The combination of heat and power in a fuel cell–gas turbine hybrid cycle provides high theoretical efficiency [1,2]. In particular, the ability to recover extra heat produced by the fuel cell into a gas turbine cycle reduces fuel required in the gas turbine system [3,4]. This provides a strong benefit in terms of emissions and fuel cost. Figure 1 shows a fuel cell–gas turbine hybrid layout, where a fuel cell may ideally replace the combustor of a typical Brayton cycle.
One of the primary barriers to commercializing these fuel cell–gas turbine hybrid systems is the simultaneous control of the various parameters that affect the performance of the cycle [5–7]. For instance, within a fuel cell–gas turbine hybrid, a minor deviation in the turbine speed affects the airflow to the cathode of a fuel cell, which affects the generation of the fuel cell waste heat that drives the gas turbine. Although several other parameters affect the fuel cell/turbine performance, the multivariable control strategy developed here was reduced to simultaneously control the turbine speed and the cathode airflow because they were both considered the two most critical parameters in the system.
In general, depending on the level of coupling/decoupling effect existing in the system, multiple parameters can be controlled using decentralized or centralized architectures [8–10]. In this work, a centralized methodology was chosen because in previous studies, Tsai et al. [11] showed that in such a hybrid configuration, a centralized multi-input multi-output (MIMO) controller was more beneficial in the control of the cross-coupling effect. In those simulations, single-input single-output controllers were evaluated against a centralized architecture, and it was found that process instabilities can occur during the simultaneous operation of the actuators when independent controllers were used, rather a centralized approach had to be adopted.
Thus, an experimental validation on the physical plant of a centralized state-space controller is the primary motivation for this work. In particular, the purpose of the study was not an optimization of the state-space controller, but aimed to evaluate the minimization of the dynamic coupling interactions existing in the physical power plant using a centralized architecture to confirm the results of the previous model based studies. In the beginning, the MIMO strategy was tested in simulation environment to prove the stability of the performance, and subsequently it was tested on the physical power plant. For the experimental validation, each control loop was individually tested before the simultaneous operation of the actuators was controlled using the MIMO architecture.
The multivariable control strategy was evaluated under turbine disturbance perturbations, turbine speed, and cathode airflow setpoint tracking maneuver. Perturbations in the turbine operation were aimed to reproduce waste heat variations caused by hypothetical fuel cell load transients, which, in general, represent the primary challenge in terms of control or disturbance rejection for a gas turbine in this hybrid configuration, whereas the setpoint tracking maneuvers evaluated the coupling created by the automated response of each individual actuator.
Results show that a centralized architecture is able to mitigate the coupling effect existing in a 2 × 2 control scenario, but different performances are shown during the validation of the MIMO controller between the simulation environment and the physical system. Although linear first-order transfer functions matched the dynamic response using single-input perturbations to the physical system, the simultaneous operation of the actuators can create behaviors that cannot be captured using simple first-order models. In the physical process, the coupling can be strong enough such that better models are required for the development and validations of future control strategies.
Background
Many studies have been performed to evaluate the most adequate control architecture for fuel cell systems in general [12–15]. In particular, the need of controlling multiple parameters on these systems focused the attention on the evaluations of decentralized and centralized control diagrams [16–18]. Generally, the development and validation of those strategies was performed in simulation environment using high detailed nonlinear models and/or linear polynomial input–output transfer functions [19,20]. Overall, it was shown that a centralized MIMO controller ensured better performance rather than single-input single-output control loops because of the capability on rejecting the coupling effect when disturbances affected the operability of the system. For instance, Mueller et al. quantified the performance of a centralized linear quadratic regulator in rejecting fuel and ambient temperature disturbances compared with a previously developed decentralized controller [20]. The development and validation of those control strategies were based on a high detailed nonlinear dynamic model implemented through mass and energy conservation principles, heat transfer calculations, and off-design compressor and turbine maps [19].
Generally, in order to develop multivariable centralized control strategies using high detailed nonlinear dynamic models, a linearization around an operating point is performed. Also, the number of states generated by the differential equations is minimized to reduce the complexity during the control strategy implementation. Using this approach, Fardadi et al. developed a centralized control strategy of a physical-based dynamic model of a single co-flow solid oxide fuel cell (SOFC) to regulate a distributed temperature profile and manage actuator interactions [21]. The centralized controller was designed using a robust methodology and results showed small and smooth monotonic temperature response to rapid and large load perturbations that reduced thermal stresses to the fuel cell material. In contrast, Pohjoranta et al. used empirical models directly identified from experimental data to implement a centralized MIMO advanced control strategy to regulate the SOFC stack temperature in a stand-alone configuration [22]. Empirical transfer functions were chosen to avoid the extensive part of physical modeling and/or model simplification for the development of the control strategy. Results were compared against a traditional single-input single-output controller, and showed that the need for a centralized control method increases especially when several stacks are built in a large SOFC systems. In such multistack systems, it was impractical to implement an optimal compensation by giving setpoints to individual stack load controllers while a centralized control does this automatically.
Similarly, Bhattacharyya and Rengaswamy used empirical nonlinear transfer functions to evaluate a centralized nonlinear MIMO controller against a single-input single-output controller [23]. The identification process was based on a detailed isothermal dynamic model of a stand-alone fuel cell that was validated with industrial data. Results showed that a well-tuned single-input single-output controller poorly performed because of the highly interactive dynamics. However, nonlinear models with properly chosen cross terms improved the model performance significantly in a MIMO problem.
Thus, based on those previous studies, empirical transfer functions directly identified from experimental tests were used here to implement a MIMO controller for the physical system. Single perturbations using unit steps to the physical process were considered an appropriate quantification methodology to capture the cross-coupling interactions among hardware components without risking the equipment. Furthermore, the experimental validation of the MIMO controller on the physical hybrid was considered an important evaluation of the state-space methodology compared to all the simulation studies presented here and generally in literature. A 2 × 2 highly coupled scenario was preferred compared to a larger case, as often proposed, because it was considered more realistic and less risky to the equipment.
Hardware
The hybrid performance (Hyper) cycle at the National Energy Technology Laboratory is designed to evaluate the dynamic integration of a fuel cell gas turbine system. Figure 2 represents the hardware components that are integrated in the hybrid configuration used in the validation of the MIMO control strategy presented in this work. Such a physical system is only designed to represent the cathode and anode pressure drop existing in the fuel cell gas turbine recuperated hybrid. Specifically, the electrochemical transients of the fuel cell do not affect the turbine operation or in other words the fuel cell is considered electrochemically inactive [24]. However, that architecture still represents a test bed facility for the development and validation of advanced control strategies because of the hardware modifications to the original gas turbine system. As such, the hybrid layout of Fig. 2 is characterized by a larger compressor plenum volume compared to the original gas turbine layout, which creates one of the main control challenges in the system operation.
Hardware Components.
At the Hyper facility, the cathode airflow can be controlled using the cold-air and/or the hot-air bypass valve [25]. The more evident coupling effect of cathode airflow control using the cold-air bypass was preferred because provided a substantial benefit in terms of system operability [26,27]. On the other hand, the electric load was used to control the turbine speed. In general, the electric load is not an actuator that adjusts the turbine speed under perturbation, but is an independent variable that changes with the external demand of electrical power. However, controlling the turbine speed using the electric load was able to examine the shaft power required to keep the turbine speed constant, and to evaluate the relationship between the turbine and the power generator for distributed applications.
Gas Turbine Generator.
A 120 kW Garrett Series 85 auxiliary power unit represented the gas turbine compressor system. A single shaft turbine and a two-stage radial compressor were designed to deliver approximately 2 kg/s of compressed airflow at a pressure ratio of about four.
Electric Load Generator.
A gear-driven synchronous (400 Hz) generator was directly coupled to the shaft of the gas turbine system, and the electrical generator was loaded by an isolated 120 kW resistor bank. Nine resistors provide the controllability of the electric load for the automated control of the system.
Cold-Air Bypass Valve.
The cold-air bypass valve was installed to bypass air from the compressor discharge directly into the turbine inlet using the mixing volume.
Swift Fuel Valve.
A Woodward swift elastomeric seat is a 2.54 cm sonic needle and nozzle operated at high-speed with a stepper motor capable of implementing fast natural gas flow changes.
Instrumentation
Speed Sensors.
Three optical sensors were installed to measure the turbine rotational speed. Each sensor picks up laser light reflected from a rotating target on the end of the generator shaft. The pulse train is transmitted to the control system, the acquisition time of the control platform is 5 ms, and sensor signals are averaged.
Cathode Airflow Meter.
The airflow is measured at the entrance of the fuel cell cathode volume using an annubar flow meter that provides a mechanical average of the difference between stagnation pressure and static pressure to determine flow.
Multivariable Controller Design
Mathematical Procedure for Multivariable Control Design.
Coupling Quantification: Relative Gain Array Analysis.
State-Space Design.
In traditional control theory, feed-forward compensations are generally added to the control action of a single-input single-output controller to improve the rejection capability of a measurable disturbance. This approach is widely used because it minimizes the coupling interaction around nominal conditions using linear transfer functions that provide a unique insight of the input/outputs properties of the system. However, as shown in simulation studies, feed-forward compensations can cause problems at off-design conditions and especially for this coupled hybrid system [30]. Thus, a state-space model is generally preferred to consider the overall cross-coupling interactions existing in hybrids. Furthermore, a state-space formulation is generally preferred for optimal design or optimal trajectory between operating states [31].
The time dependence in x, u, and y is usually omitted, whereas A, B, C, D are real matrices and considered time-invariant linear systems. The first equation shows how the inputs influence each state, whereas the second equation shows how the states and the inputs influence the outputs.
State-Space Stability Analysis.
In this case, the eigenvalues of the (A − B · K) matrix provide the stability criteria for the closed-loop system. In other words, the effect of the K matrix controller on the open-loop roots is evaluated by showing the location of the closed-loop roots.
State-Space Controllability Analysis.
The state-space system is completely controllable if and only if the P controllability matrix defined in Eq. (8) has full rank, or in other words the determinant of P is equal to the number of states.
Internal Model Control Approach.
In terms of control performance, zero steady-state error is an important requirement not only for disturbance rejection but also for reference tracking. In general, the reference input considered can include steps, ramps, and other persistent signals, such as sinusoids. For a step input, it is known that zero steady-state tracking errors can be achieved with a type-one system [32,33]. This idea is formalized by introducing an “internal model” of the reference input in the controller as shown in Fig. 3 in order to include an integrator in the feed-forward path between the error comparator and the plant.
The corresponding block diagram that includes an internal model, which is basically an integrator of the reference step inputs, is shown in Fig. 3.
Design of the Multivariable Architecture.
The dimension of the K matrix is related to the dimension of the states matrix (A) and inputs matrix (B) in the state-space formulation. Specifically, the number of columns is equal to the number of states and the number of rows is equal to the number of actuators in the system. The main advantage of using a matrix representation as a control strategy is the mitigation of the decentralized coupling. In particular, the decentralized items in the K matrix represent compensation in the control action that is proportional to those states that shows a coupling effect in the system. Such a compensation provides a “communicative effect” or “anticipation” factor in the control action, which diminishes the influence that adjacent actuators have on each state or output during simultaneous control. The communicative effect for the control problem designed in this work is illustrated in Fig. 4. Such an approach was similar to what Tsai et al. mentioned in a previous simulation study [11].
The controller design was performed through the “place” function available in matlab. The states matrix (A), the inputs matrix (B), and the desired pole locations need to be specified in order to compute a controller (K) matrix. The desired pole locations were developed by computing the damping factor and the natural frequency in the step response of the desired characteristic equation, or in other words by determining the coefficient in Eq. (11). The controller response was quantified by evaluating the settling time of the step response applied to the desired characteristic equation in the Simulink environment. Finally, a closed-loop stability analysis was performed using Eq. (7).
Multivariable State-Space Derivation for the Physical Hybrid Cycle.
Compared to previous work, new transfer functions were experimentally developed because of hardware changes in the Hyper facility affected the reliability of those earlier models [29]. Each transfer function was developed using a single step in the linear operating range while the system was running at nominal conditions, as shown in Figs. 5 and 6. The accuracy in the dynamic response was verified by fitting each function against experimental data.
A 20 kW electric load variation was performed in Fig. 5 to develop single-input single-output transfer functions for turbine speed and cathode airflow. A scaling approach was used to avoid any discrepancies between the different engineering units: rpm, kW, %, kg/s, etc. As shown in Fig. 5, the transfer function models matched the experimental transient, when a step in the turbine electric load was performed, the turbine speed is affected by more than 2000 rpm, and the coupling on the cathode airflow is about 0.13 kg/s.
Coupling Quantification: Relative Gain Array Analysis.
State-Space Design.
The time in Eq. (18) was omitted, and e1 was the error between the turbine speed setpoint and the turbine speed feedback, while e2 was the error between the cathode airflow setpoint and the cathode airflow feedback.
Stability Analysis.
The stability analysis of the open-loop model in Eq. (17) yielded root locations in −0.22 and −1.43, which means that the system was simply stable in open-loop. On the other hand, the stability analysis of the open-loop model using the IMC approach illustrated in Eq. (18) produced two additional roots that were both located in the origin. In this case, the augmented system was asymptotically stable, and presented four roots located in the following positions: .
Controllability Analysis.
The size of the P controllability matrix related to the open-loop state-space model in Eq. (17) was 2 × 4 and the rank was 2, which means that the system was completely controllable. Similarly, the size of the P controllability matrix of the augmented state-space model presented in Eq. (18) was 4 × 8 and the rank was equal to 4; therefore, even in this case, the system was completely controllable.
Multi-Input Multi-Output Disturbance State-Space Design.
Design of the Multivariable Architecture.
The K matrix of the state feedback controller using the IMC representation in Eq. (18) was composed by two rows and four columns. The first row of gains was associated with the turbine speed-electric load control loop, whereas the second row of gains was associated with the cold-air bypass-cathode airflow control loop. Considering the individual items in the K matrix, k11 represented the integral gain and k13 the proportional gain for the turbine speed-electric load control loop, whereas k22 and k24 represented the integral gain and the proportional gain for the cold-air bypass-cathode airflow control loop. Since a turbine speed change affected the cathode airflow almost instantaneously, k23 provided an additional benefit to the control action of the cold-air bypass valve, which yielded an instantaneous change in the cathode airflow as soon as a perturbation in the turbine speed occurred. Similarly, k14 provided an additional benefit to the electric load command when the cold-air bypass valve modulated the cathode airflow and affected the turbine speed. On the other hand, k12 was not included in the architecture because an additional compensation in the electric load command based on the integral action of the cathode airflow control loop would only have increased the oscillation in the process. Integral actions are very important to keep zero steady-state difference but creates undesirable windup because accumulates the error between the reference value and the feedback measurement over time. Similarly, k21 was not included because an additional compensation on the cold-air bypass valve control command based on the integral action of the turbine speed control loop would have increased the oscillation in the process as well. Figure 4 presents the control architecture with the communicative effect involved.
Experimental Methodology
The thermal steady-state provides the required stability in the system that has to be generally guaranteed before connecting any control strategy to the physical plant. This condition is achieved when the turbine speed reaches 40,500 rpm and the skin temperature of the mixing volume varies less than 0.1 K for a 30 s period. During the startup procedure, a single-input single-output proportional, integral, derivative controller increases the turbine speed up to the nominal setpoint by ramping up the fuel flow into the combustor. To ensure sufficient surge margin to the compressor during turbine speed ramp up, the bleed-air valve and the cold-air bypass are set to 90% closed and 40% open position, respectively. This corresponds to approximately 3% of the compressor flow bled through the bleed-air valve and 26% of the compressor flow diverted through the cold-air bypass.
When the system operates at thermal steady-state condition and 40 kW of electric load are engaged to the turbine shaft, the fuel valve speed controller is disconnected. In this case, the turbine operates at constant fuel flow, which is generally considered an open-loop configuration. This represents a temporary operation before connecting the control strategy.
Once the system operated in open-loop configuration, the multivariable control strategy was connected to control the hardware system, and three different set of experiments were designed. For each set of experiment, three different tests evaluated the performance of the strategy. As shown in Table 1, in the first set of experiments, only the electric load–turbine speed control loop was connected to the hardware, and only two tests were evaluated. In the first test, the turbine speed setpoint tracking operation evaluated the coupling on the cathode airflow during the sole automated control of the electric load, whereas in the second test, the fuel valve perturbation simulated the waste heat variation of the fuel cell stack.
Experiment | Test 1 | Test 2 | Test 3 |
---|---|---|---|
Electric load–turbine speed | Turbine speed setpoint (500 rpm) | Fuel valve perturbation 200 kWth (35 kWel in the fuel cell) | N/A |
Cold-air bypass–cathode airflow | N/A | N/A | Cathode airflow setpoint (0.2 kg/s) |
Multivariable strategy (Fig. 4) | Turbine speed setpoint (500 rpm) | Fuel valve perturbation 200 kWth (35 kWel in the fuel cell) | Cathode airflow setpoint (0.2 kg/s) |
Experiment | Test 1 | Test 2 | Test 3 |
---|---|---|---|
Electric load–turbine speed | Turbine speed setpoint (500 rpm) | Fuel valve perturbation 200 kWth (35 kWel in the fuel cell) | N/A |
Cold-air bypass–cathode airflow | N/A | N/A | Cathode airflow setpoint (0.2 kg/s) |
Multivariable strategy (Fig. 4) | Turbine speed setpoint (500 rpm) | Fuel valve perturbation 200 kWth (35 kWel in the fuel cell) | Cathode airflow setpoint (0.2 kg/s) |
In the second set of experiments, the electric load–turbine speed control loop was disconnected and the cold-air bypass–cathode airflow control loop was connected to the hardware. In this case, only a cathode airflow setpoint variation was performed, which evaluated the coupling on the turbine speed during the sole automated control of the cold-air bypass valve. Finally, in the third set of experiments, the multicoordination strategy with the communicative effect presented in Fig. 4 was connected to control the hardware system, and all of the three tests evaluated the performance of the strategy.
During each experiment, one test and so one perturbation at the time was performed while all the other actuators were set at constant position. Table 2 summarizes the operating point of the system during each test for all the experiments.
Actuator position | Exp. 1, test 1 | Exp. 1, test 2 | Exp. 2, test 3 | Exp. 3, test 1 | Exp. 3, test 2 | Exp. 3, test 3 |
---|---|---|---|---|---|---|
Electric load | Automated | Automated | 40 kW | Automated | Automated | Automated |
Cold-air bypass | 40% | 40% | Automated | Automated | Automated | Automated |
Bleed-air valve | 90% closed | 90% closed | 90% closed | 90% closed | 90% closed | 90% closed |
Hot-air bypass (%) | 25 | 25 | 25 | 25 | 25 | 25 |
Skin temperature (° F) | 1252 | 1255 | 1270 | 1265 | 1244 | 1271 |
Fuel valve (%) | 51.3 | 51.2–55.2 | 51.2 | 51.3 | 51.3–55.3 | 51.3 |
Actuator position | Exp. 1, test 1 | Exp. 1, test 2 | Exp. 2, test 3 | Exp. 3, test 1 | Exp. 3, test 2 | Exp. 3, test 3 |
---|---|---|---|---|---|---|
Electric load | Automated | Automated | 40 kW | Automated | Automated | Automated |
Cold-air bypass | 40% | 40% | Automated | Automated | Automated | Automated |
Bleed-air valve | 90% closed | 90% closed | 90% closed | 90% closed | 90% closed | 90% closed |
Hot-air bypass (%) | 25 | 25 | 25 | 25 | 25 | 25 |
Skin temperature (° F) | 1252 | 1255 | 1270 | 1265 | 1244 | 1271 |
Fuel valve (%) | 51.3 | 51.2–55.2 | 51.2 | 51.3 | 51.3–55.3 | 51.3 |
Comparing Simulation and Experimental Results
Electric Load-Turbine Speed.
The evaluation of each single-input single-output control loop was considered important to quantify the coupling effect when only one actuator at the time was set in automated mode. In these two single-input single-output cases, the cathode airflow or the turbine speed was alternatively set in open-loop configuration, and only the centralized items from the K matrix of Eq. (21) were considered without involving the communicative effect between control loops. The controller structure was essentially based on a linear combination at discrete time steps (5 ms) that only included the proportional and the integral gains of each loop. Specifically, only the gains k13 and k11 were used in the first control loop (electric load–turbine speed, experiment 1 in Table 1), and the gains k22 and k24 were used in the second control loop (cold-air bypass–cathode airflow, experiment 2 in Table 1), which all were designed using a multivariable state-space concept.
Experiment 1—Test 1: Turbine Speed Set-Point.
During a change in the electric load, the turbine operates in a variable speed mode affecting the cathode airflow. The dynamic response of the turbine strongly affects the performance of the entire system, and a deviation in the nominal operating point influences the overall mass flow, pressure, and temperature of the entire fuel cell/gas turbine cycle. For instance, a speed reduction reduces the cathode inlet airflow that causes a decrease in the dissipation of the thermal energy from the fuel cell to the turbine [25]. In this scenario, the turbine speed and the compressor inlet airflow decrease even more than the initial turbine speed setpoint change and a stall of the compressor can easily occur, damaging the fuel cell [27].
Considering all these important dynamic effects, the turbine speed setpoint change in Fig. 7 was used to quantify the impact of coupling on the cathode airflow although the fuel cell was electrochemical inactivity. During this test, a turbine speed was perturbed by only 500 rpm, which represents 1.2% of the full range of operation. The cathode airflow was set equal to 0.77 kg/s, slightly below 1.0 kg/s, which represents the typical nominal operating point of fuel cell sized for the Hyper facility.
The comparison between the simulated and the experimental results presented in Fig. 7 shows significant differences in the performance of the controller. For instance, the simulated trend confirms that the overdamped tuning was an adequate design because the turbine speed properly approaches the new setpoint without overshoot. On the other hand, an underdamped behavior characterized the response of the controller in the experimental test, although the original design was still based on an overdamped tuning. Specifically, the rise time between the experimental and the simulated performance of the controller was approximately identical, indeed the time for the output to reach 90% of its final value was in both cases approximately 1.28 s. Instead, the settling time between the experimental and the simulated test showed a difference of about 6–8 s due to the overshooting in the turbine operation. The inconsistency between the controller design and the performance on the hardware system was due to the order of the mathematical model. Although each first-order transfer function matched the experimental transients as shown in Figs. 5 and 6, often the dynamic of a first-order model is very similar to an overdamped second-order transfer function. This can mislead to approximate such a transient behavior with a first-order model in a second-order system. A mismatch in the controller performance between simulation and experimental environment can occur as shown in Fig. 7. A first-order model generally lacks underdamped dynamics.
Furthermore, Fig. 7 shows that the gains k13 and k11 designed in Eq. (21) cause 200 rpm of overshooting, which is 0.5% of the overall turbine speed range. However, it still represents a significant deviation considering that the amplitude of the step was equal to 500 rpm. The maximum rate of change for the electric load command to manage the turbine speed setpoint variation was equal to 1.5 kW in a single time-step (80 ms), and produced a change of 18 kW in 3.2 s. Such a response was difficult to be predicted in simulation environment because the accuracy of the simulated actuator is more precise than the physical one. In other words, the physical actuator has an accuracy of 0.5 kW in a single time-step (5 ms), which limits the precision of the response compared to the simulation study. These effects confirm the challenge of testing control strategies on physical hardware systems.
Similar differences between simulation and experimental trends are presented in the steady-state difference of the cathode inlet airflow. The model quantified a steady-state difference of about 0.1 kg/s due to the sole implementation of the single-input single output controller whereas, the experiment only presents an oscillation of that amount of deviation, and the final steady-state difference between the cathode airflow setpoint (0.77 kg/s) and the plant output is less than half of that. In this case, the oscillation could still damage the fuel cell material, but it confirmed the strong influence that the turbine speed has on the fuel cell airflow.
Experiment 1—Test 2: Fuel Valve Perturbation.
In this experiment, the fuel cell was still electrochemically inactive and so a change in the fuel flow of the gas turbine combustor was used to simulate a hypothetical fuel cell waste heat variation. Similarly to the previous case, in the results shown in Fig. 8, the turbine was still controlled through the single-input single-output load-based speed controller designed using the gains k11 and k13 (Eq. (21)). In other words, the cathode airflow was intentionally left in open-loop to evaluate the coupling effect under heat perturbations performed through fuel flow variations.
As an example of the magnitude of change, an off-line fuel cell simulation was performed to quantify the heat variation presented in Fig. 8 using a 4% fuel valve step perturbation. This slight change yields a thermal heat deviation from a hypothetical fuel cell to the turbine equal to 200 kWth. Such a deviation represented a fuel cell load turn down of about 30 A over an operating range of 200 A, which means a 15% of deviation in the fuel cell current demand around nominal conditions. In terms of fuel cell electric power generation, the fuel valve change reproduced a deviation of about 35 kWe over an operating range of 350 kWe, which means a deviation of about 10% around nominal fuel cell power conditions. In open-loop, a fuel valve perturbation of 4% caused almost 3000 rpm of turbine speed deviation in about 40 s.
In this case, the controller quickly handled the significant variation of thermal energy by keeping the speed within a safe boundary of nominal operation; indeed, a deviation of just 300 rpm affected the response. Similarly to the previous case, the experiment shows a larger perturbation compared to the simulation results. The turbine speed and the cathode airflow were, respectively, affected by 150 rpm and 6% more in the experiment compared to the simulation results. Also, the electric load control action that keeps the system at steady condition is different; a more consistent electric load change during the experiment to reject the disturbance on the speed operation was maintained compared to the simulation. Specifically, the electric load was changed about 16.5 kW in about 9 s when the step was applied, and the maximum rate was equal to 1 kW in a single time-step (80 ms). Hence, the controller provides stable operation, quick time response, and a pronounced rejection capability when the step was applied to the turbine combustor. In this test, the cathode airflow was not controlled, and a 6% variation was noticed around nominal condition during this perturbation. A pronounced rejection capability for the turbine speed controller provided an important benefit to maintain the cathode airflow around nominal conditions.
Cold-Air Bypass-Cathode Airflow.
Once the electric load–turbine speed control loop was validated, the single-input single-output cold-air bypass cathode mass flow controller was implemented and tested in the hardware system (experiment 2 in Table 1). In this case, only the centralized items from the second row of the K matrix in Eq. (21) were considered in the structure of the controller. The gains k24 and k22 represent the proportional and the integral gains, respectively, which were designed using the multivariable state-space procedure.
Experiment 2—Test 3: Cathode Airflow Set-Point.
In a fuel cell/gas turbine hybrid system, a cathode airflow maneuver can be used to control the temperature difference between the inlet and the outlet of a fuel cell stack [25]. In this scenario, a regulator rather than a controller can be preferred to manage the operating point of the solid temperature in the fuel cell material. However, the high coupling between the cold-air bypass and the turbine speed can create control issues, and a quantification is presented in Fig. 9.
In this case, the difference between the simulation and experimental performance was more significant compared to the previous tests especially, in the automation of the valve that handles the airflow setpoint change, and in the coupling of the turbine speed. The simulated trend in the cathode airflow performance follows the step change almost instantaneously due to the very reactive response of the cold-air bypass valve. On the other hand, the experimental trend is significantly delayed due to hardware limitations in the sensor measurement and in the actuation of such a valve. Specifically, during the experiment, the controller opened the cold-air bypass valve by 25% in 13 s, using a maximum rate of 0.7% in a single time-step (80 ms), whereas in simulation, the valve was able to provide a 40% change in less than a couple of seconds. Such inconsistency was probably due to underdamped dynamic effects that were not completely captured in the input–output model between the valve and the process. For instance, even increasing the transport delay in the system model between the valve opening and the process did not improve the response. This simulation created an even faster opening in the valve to compensate a negligible change in the process reaching the saturation point more quickly.
Although the fuel cell was still electrochemically inactive, an automated control of the cold-air bypass valve created a larger coupling on the turbine speed compared to the quantification shown in the simulation of the model. The setpoint change in the cathode airflow was equal to 0.2 kg/s, and almost 1000 rpm of coupling occurred in the turbine operation even without electrochemical dynamics taken into account during the experimental test. Such a coupling is primarily due to the action of the cold-air bypass valve that reduces the turbine inlet temperature bypassing cold airflow from compressor discharge to the turbine inlet.
Multivariable Strategy.
Once the performance of each control loop was individually validated, the multivariable control strategy with the communicative effect presented in Fig. 4 was simultaneously connected to the hardware system. Considering the test matrix of Table 1, all of three tests in the third experiment were experimentally performed.
Experiment 3—Test 1: Turbine Speed Set-Point.
Figure 10 presents a turbine speed setpoint tracking maneuver equal to 1.2% of the full range of operation during a simultaneous control of actuators. This test was considered important to quantify the coupling effect on the cathode airflow when the turbine speed changes, and simultaneously, the cold-air bypass controls the cathode airflow.
Similarly to the single-input single-output case, the multivariable control strategy presented in Fig. 10 shows different performance between the simulation and the experimental test. The simulated response was characterized by an overall overdamped behavior for both actuators, as properly defined in the design process. On the other hand, the experimental response presented an underdamped behavior in the operation of the turbine and a more pronounced overdamped behavior in the response of the cold-air bypass valve to reject the coupling on the cathode airflow compared to the simulation trend. As previously described, such inconsistency was due the mathematical model of the system that was used to design the response of the control strategy. In other words, the turbine speed model lacked underdamped dynamics that exists in the real power plant, and the model of the cold-air bypass valve does not reproduce hardware limitations in the actuator and in the sensor measurement.
However, in this case, the turbine speed overshoot is 190 rpm, and similarly to Fig. 7 represents a significant deviation considering only 500 rpm of setpoint change. Similarly to the single-input single-output case, the maximum rate of change of the electric load command was 1.5 kW in a single time-step (80 ms). As in the previous case, the electric load response produced an excessive overshooting in the turbine speed that was not properly quantified in the off-design tuning of the controller and in the modeling of the system. Such a turbine oscillation also caused an instantaneous fluctuation on the cathode airflow, which was not similarly predicted by the model. This coupling effect was not entirely rejected due to the slow response of the overdamped design used in Eq. (21), and due to hardware limitations existing in the actuation of the valve and in the sensor measurement. However, the simultaneous operation of the cold-air bypass valve avoids cathode airflow steady-state difference that existed in the single-input single-output case shown in Fig. 7 (experiment 1, test 1).
The maximum rate of change of this actuator was only equal to 0.14% for a single time-step (80 ms). The fuel cell would be able to tolerate this oscillation because the coupling caused by the turbine speed on the cathode airflow was at the limit of 0.05 kg/s. However, a larger change in the speed would cause a higher coupling on the cathode airflow that could be detrimental to the fuel cell, especially if such an overdamped designed is still used.
Experiment 3—Test 2: Fuel Valve Perturbation.
Similar to the single-input single-output case of Fig. 8, Fig. 11 presents a fuel valve step perturbation that reproduces a waste heat variation due to an increase of a hypothetical fuel cell load change, but during a simultaneous control of actuators.
As well as for the single-input single-output case, the significant variation of thermal energy (200 kWth) that affected the turbine speed operation was properly handled by the electric load. The controller provided a change of 18.5 kW in about 4.08 s, and the maximum rate of change was 1 kW in a single time-step (80 ms). Similarly to the previous case, the quick response and the pronounced rejection capability on the turbine speed provided the most important benefit on the minimization of the coupling on the cathode airflow. Indeed, a deviation of just 300 rpm affected the turbine speed when the heat perturbation was applied, and the airflow was kept steady during such a transient.
Compared to Fig. 9, the cathode airflow did not present steady-state difference because it was controlled by the cold-air bypass valve, but presented a similar oscillation when the fuel flow perturbation was applied. Even in this case, the over-damped design limited the rejection of the coupling effect on the cathode airflow. The maximum rate of change of the cold-air bypass valve was only equal to 0.1% for a single time-step (80 ms). The coupling effect of a hypothetical fuel cell load perturbation on the cathode airflow is just 0.03 kg/s, and the fuel cell would be able to tolerate this oscillation. If the fuel cell had been electrochemically active, the oscillation in the cathode airflow would have affected the turbine speed even more, due to the self-propagated effect existing in the hybrid configuration. However, the turbine speed controller responded pretty quickly, and this confirms that constant turbine speed operation, or an excellent rejection capability for turbine speed perturbations, minimized the coupling effect on the cathode airflow.
As well as for the single-input single-output case, a larger deviation in the turbine speed and a more consistent electric load change were shown in the experimental test compared to the simulation results. In this case, such inconsistency does not affect significantly the controller performance, but still presents the need for a better quantification of the dynamic response in the modeling of the system and during the design of the controller.
Experiment 3—Test 3: Cathode Airflow Set-Point.
Similarly to the single-input single-output case of Fig. 9, Fig. 12 presents the cathode airflow setpoint tracking variation, but during simultaneous control of actuators. The amplitude for the cathode airflow variation was kept equal to 0.2 kg/s.
Figure 12 shows that the simultaneous control of the electric load rejected 1000 rpm of coupling on the turbine speed during the automated control of the cold-air bypass valve to track the cathode airflow setpoint change presented in Fig. 9. Specifically, the control strategy was able to open the cold-air valve by 30%, and reduced the electric load from 40.5 kW down to 33.5 kW to keep the turbine speed constant. The maximum rate of change for the cold-air bypass valve was equal to 0.6% in a single time-step (80 ms), and for the electric load command to maintain the turbine speed constant was 0.5 kW. However, a few spikes showed in dashed circles in Fig. 12 affected the turbine speed around nominal conditions. A robust design in future work could be preferable to avoid detrimental instabilities on the turbine shaft.
Similarly to the single-input single-output case, the multivariable control strategy presented the same limitation in the comparison between the simulation and experimental results. For instance, the simulated response of the cold-air bypass valve showed a more reactive behavior that provided an accurate tracking of the airflow setpoint change. On the other hand, the physical actuator has a slower response that affected the airflow tracking due to an inaccuracy in the model of the valve.
Summary and Conclusions
This paper showed an experimental evaluation of a 2 × 2 multivariable control strategy applied to a gas turbine recuperated cycle designed for a fuel cell/gas turbine hybrid concept. State-space methodology was used to quantify the dynamic performance of the physical plant. In this scenario, the fuel cell was electrochemical inactive, but the control of the physical hybrid plant was still a challenge due to the large size of the compressor plenum volume, which represents the cathode and anode pressure drop in the hybrid configuration. In the experiments, the electric load was used to control the turbine in order to evaluate the relationship between the speed and the power generator, whereas the cathode airflow was controlled using the cold-air bypass valve, which showed a strong coupling on the turbine speed. The control strategy was evaluated under heat disturbance perturbation that represented a hypothetical fuel cell load variation, and turbine speed and cathode airflow setpoint tracking maneuver.
An overall inconsistency was shown between the designed performance in simulation environment and the response of the power plant due to hardware limitations in the sensor measurement, actuation of the valves, and underdamped dynamic effects that were difficult to be captured with the first-order dynamic model that was used to design the control strategy. For instance, during turbine speed setpoint tracking change, an overdamped designed produced an underdamped behavior, and a significant peak overshooting from the setpoint occurred. In general, it was shown that for hybrid systems, a turbine speed deviation for more than a few seconds generates strong coupling on the cathode airflow that can be detrimental for the fuel cell operation. Furthermore, the same set of gains that well perform for disturbance rejection can cause an excessive response for setpoint tracking operation.
During heat perturbation, the shaft power required to maintain constant turbine speed operation was equal to 16 kW of change in the electric load when a hypothetical 10% (200 kWth) of fuel cell load turn down operation was reproduced. The coupling in the cathode airflow was minimized and kept below a 5% limit that avoids fuel cell damage. However, the cold-air bypass valve showed a slow response due to hardware limitations and inaccuracy in the underdamped dynamics of the first-order model used to characterize the cold-air bypass-cathode airflow response to tune the controller.
Finally, although the fuel cell was electrochemically inactive, a 0.2 kg/s of cathode airflow perturbation caused almost 1000 rpm of change in the turbine speed operation due to the effect of the cold-air bypass valve. During the simultaneous control of actuators, the multivariable control strategy was able to keep the turbine speed constant. This test presented the most significant difference in the response of the controller between simulation and experimental behaviors due to hardware limitations in the physical system. However, the overall comparison between simulation and experimental results of the multivariable control strategy presented in this paper shows that the coupling in hybrid power systems can be strong enough such that even linear transfer functions can be inadequate to describe fluid and turbomachinery behaviors occurring during transients.
Future Work
As mentioned, in this work, the fuel cell was electrochemical inactive to avoid critical damaging to the turbine equipment during the simultaneous operation of the actuators. However, future work will evaluate the multivariable control strategy during the electrochemical activity of the fuel cell. In this case, the coupling between cathode airflow and turbine speed can be very detrimental due to the self-propagated effect between fuel cell and turbine transient [25]. Gains optimization and the communication effect in the multivariable control strategy will definitely play a critical role to minimize the coupling interactions. Higher-order mathematical models in the discrete time domain will be directly included in the state-space representation to identify a larger range of frequencies in the system, and to more precisely quantify the time delay as time steps of delay. Optimal control tuning, robust and adaptable design of novel control strategies will be also compared to this baseline control problem [35].
Acknowledgment
This work was supported by the U.S. Department of Energy, Office of Fossil Energy, Crosscutting Research program, implemented through the Technology Development and Integration Center, Coal. The research was performed by the Ames Laboratory in collaboration with the U.S. Department of Energy's National Energy Technology Laboratory.
Funding Data
Office of Fossil Energy (Grant No. DE-AC02-07CH11358).
Nomenclature
- A =
states matrix in the state-space formulation
- =
states matrix of the desired response
- B =
inputs matrix in the state-space formulation
- C =
output matrix in the state-space formulation
- g =
transfer function in the Laplace domain
- G =
matrix transfer function
- k =
transfer function gain
- p =
pole location in the frequency domain
- s =
Laplace variable
- u =
input vector
- ua =
input vector augmentation
- ud =
disturbance input vector
- u1 =
electric load
- u2 =
cold-air bypass valve
- u3 =
fuel valve gas turbine combustor
- u4 =
hot-air bypass valve
- x =
state vector
- xa =
state vector augmentation
- x1 =
turbine speed error
- x2 =
cathode airflow error
- x3 =
turbine state feedback
- x4 =
cathode airflow feedback
- y =
output vector
- y1 =
turbine speed error
- y2 =
cathode airflow error
- Δu =
input variation
- Δy =
output variation
- ϑ =
time delay
- =
Hadamard product operator, element by element multiplication